Published February 1982 | Version v1
Report Restricted

San Onofre/Zion auxiliary feedwater system seismic fault tree modeling

Description

As part of the study for the seismic evaluation of the San Onofre Unit 1 Auxiliary Feedwater System (AFWS), a fault tree model was developed capable of handling the effect of structural failure of the plant (in the event of an earthquake) on the availability of the AFWS. A compatible fault tree model was developed for the Zion Unit 1 AFWS in order to compare the results of the two systems. It was concluded that if a single failure of the San Onofre Unit 1 AFWS is to be prevented, some weight existing, locally operated locked open manual valves have to be used for isolation of a rupture in specific parts of the AFWS pipings

Availability note (English)

MF available from INIS under the Report Number; Available from NTIS., PC A03/MF A01 as DE82019241.

Files

Restricted

The record is publicly accessible, but files are restricted to users with access.

Additional details

Publishing Information

Imprint Pagination
39 p.
Report number
UCRL--15491