Analysis of core damage frequency due to external events at the DOE [Department of Energy] N-Reactor

  • 1. Sandia National Labs., Albuquerque, NM (USA)
  • 2. Westinghouse Hanford Co., Richland, WA (USA)
  • 3. EQE, Inc., San Francisco, CA (USA)
  • 4. ERCE, Inc., Albuquerque, NM (USA)

Description

A complete external events probabilistic risk assessment has been performed for the N-Reactor power plant, making full use of all insights gained during the past ten years' developments in risk assessment methodologies. A detailed screening analysis was performed which showed that all external events had negligible contribution to core damage frequency except fires, seismic events, and external flooding. A limited scope analysis of the external flooding risk indicated that it is not a major risk contributor. Detailed analyses of the fire and seismic risks resulted in total (mean) core damage frequencies of 1.96E-5 and 4.60E-05 per reactor year, respectively. Detailed uncertainty analyses were performed for both fire and seismic risks. These results show that the core damage frequency profile for these events is comparable to that found for existing commercial power plants if proposed fixes are completed as part of the restart program. 108 refs., 85 figs., 80 tabs

Availability note (English)

MF available from INIS under the Report Number; NTIS, PC A24/MF A01 as DE91004666; OSTI; INIS; US Govt. Printing Office Dep.

Files

22032110.pdf

Files (25.8 MB)

Name Size Download all
md5:c14707958a2bc07617329525143007ef
25.8 MB Preview Download

Additional details

Publishing Information

Imprint Pagination
568 p.
Report number
SAND--89-1147

Optional Information

Contract/Grant/Project number
Contract AC04-76DP00789