Influence of Water Sub-Cooling on Discharge Characteristics in a Water Storage Tank
Creators
- 1. Nuclear Power Institute of China, Chengdu, Sichuan 610041 (China)
Description
The influences of water sub-cooling on water discharge behaviors from the water storage tank were studied experimentally with a test rig, which consists of a water vessel, a steam supplier, valves and piping. From this study, it is found that the gravitational discharging process is effected strongly by the steam condensation, taking place between steam and cold water in the vessel during discharge. Increased sub-cooling of the water, enhances the steam condensation, and promotes a deeper penetration of steam into water. The two modes of condensation identified in this study are: steam-supply-limit-mode and steam-condensation-limit-mode. The first mode occurs at the primary discharge period if water sub-cooling is large than a certain value, for example, 50 deg. C sub-cooling in this study. Conclusions were derived based on this study for the impact of subcooling on discharge characteristics with respect to flow, pressure, and other parameters. Some suggestions to avoid or reduce undesired phenomena are also presented. (authors)
Additional details
Publishing Information
- Publisher
- American Society of Mechanical Engineers - ASME
- Imprint Place
- New York (United States)
- Imprint Pagination
- 10 p.
Conference
- Title
- 10. international conference on nuclear engineering
- Acronym
- ICONE-10
- Dates
- 14-18 Apr 2002
- Place
- Arlington - Virginia (United States)
INIS
- Country of Publication
- United States
- Country of Input or Organization
- France
- INIS RN
- 39086249
- Subject category
- S42: ENGINEERING;
- Resource subtype / Literary indicator
- Conference
- Descriptors DEI
- AVAILABILITY; STEAM; STORAGE; SUBCOOLING; TANKS; VALVES; WATER
- Descriptors DEC
- CONTAINERS; CONTROL EQUIPMENT; COOLING; EQUIPMENT; FLOW REGULATORS; HYDROGEN COMPOUNDS; OXYGEN COMPOUNDS