High-range containment radiation monitor response to post-accident fission product releases

  • 1. Sargent and Lundy, Chicago, IL

Description

Two high-range containment radiation monitors (HRCRMs) have been installed in the drywell at the James A. FitzPatrick nuclear power station. These monitors were initially required only to provide a reasonable assessment of area radiation conditions inside the containment following a design basis accident. Recently, however, in addition to the original requirement, these monitors have been considered as a means for obtaining a gross estimate of core damage following an accident. One way to obtain this estimate is to correlate the HRCRM reading with a set of precalculated readings based on a series of hypothetical core fission product releases. These HRCRM readings can be used as an indicator of the airborne radioactivity potentially available for release. The results of this study indicate that within reasonable bounds the HRCRM response is not extremely sensitive to either detector location or contained sources

Additional details

Publishing Information

Journal Title
Trans. Am. Nucl. Soc.
Journal Volume
50
Series
Trans. Am. Nucl. Soc.
Journal Page Range
464-465
ISSN
0003-018X
CODEN
TANSA

Conference

Title
American Nuclear Society winter meeting.
Dates
10-15 Nov 1985.
Place
San Francisco, CA (USA).

Optional Information

Secondary number(s)
CONF-851115--.