Published April 15, 2019 | Version v1
Journal article

Thermodynamic analysis of a direct expansion solar-assisted heat pump system working with R290 as a drop-in substitute for R22

  • 1. National Institute of Technology Calicut, Department of Mechanical Engineering (India)

Description

The thermodynamic analysis of direct expansion solar-assisted heat pump system working with R290 as a drop-in substitute for R22 was carried out under the metrological conditions of Calicut, India. A prototype of a DXSAHP system consists of a compressor, an air-cooled condenser with evaporator–collector and thermostatic expansion valve. The experiments were carried during the winter months of 2016. The artificial intelligence technique artificial neural network integrated with genetic algorithm model was presented to predict energy and exergy performance of a system. The energy performance ratio of a system was found to be 5.75% higher and reduced heating capacity of about 6.8% when compared to R22. Similarly, the second law analysis (exergy analysis) of a total system working with R290 was found to be better when compared to baseline refrigerant. The selected alternative working fluid is a hydrocarbon and has zero ozone depletion and negligible global warming potential. Hence, R290 can be used as a drop-in substitute for R22 in DXSAHP systems.

Additional details

Identifiers

Publishing Information

Journal Title
Journal of Thermal Analysis and Calorimetry
Journal Volume
136
Journal Issue
1
Journal Page Range
p. 63-78
ISSN
1388-6150

Optional Information

Copyright
Copyright (c) 2019 Akademiai Kiado, Budapest, Hungary