Assessment of occupational exposure to magnetic fields in high-voltage substations (154/34.5 kV)
Creators
- 1. Dept. of Electrical and Electronics Engineering, Engineering Faculty, Akdeniz Univ., 07058 Antalya (Turkey)
Description
This work proposes the survey of magnetic field measurements taken in 154/31.5 kV substations in the city of Antalya for occupational exposure assessment. For measurements, three substations have been taken into account, where four occupants are present for each 8 h of shift, which means 12 occupants are present during the day. Operator desks at three different substations read a lowest magnetic field of 0.3 μT at minimum loaded season and reached up to 1 μT at maximum loaded season, which means operators exposed to a magnetic field of ≥ 0.3 μT 8 h d-1. In switch gear regions, maximum magnetic field reading is 23 μT at minimum loaded season and reached up to 70 μT. Outdoor magnetic field measurement at circuit breaker region goes up to 62 μT with respect to operator heights. (authors)
Availability note (English)
Available from doi: http://dx.doi.org/10.1093/rpd/ncm443Additional details
Identifiers
- DOI
- 10.1093/rpd/ncm443;
Publishing Information
- Journal Title
- Radiation Protection Dosimetry
- Journal Volume
- 128
- Journal Issue
- 4
- Journal Page Range
- p. 464-470
- ISSN
- 0144-8420
INIS
- Country of Publication
- United Kingdom
- Country of Input or Organization
- France
- INIS RN
- 43120551
- Subject category
- S61: RADIATION PROTECTION AND DOSIMETRY; S63: RADIATION, THERMAL, AND OTHER ENVIRONMENTAL POLLUTANT EFFECTS ON LIVING ORGANISMS AND BIOLOGICAL MATERIALS;
- Descriptors DEI
- ELECTROMAGNETIC FIELDS; HUMAN POPULATIONS; MAGNETIC FIELDS; OCCUPATIONAL EXPOSURE; POWER PLANTS; RADIATION MONITORING
- Descriptors DEC
- MONITORING; POPULATIONS
Optional Information
- Notes
- 13 refs