Leakage investigation in an underground cooling water pipeline at a thermal power station using radiotracer technique

Description

The objective of this study was to locate the leakage point(s) in an underground cooling water pipeline of a Thermal Power Station for pre-shutdown planning purposes. The internal diameter of the pipeline was 2240 mm with 12 mm with 12 (mild steel) wall thickness and it was buried under 1.0 meter reinforced concrete and 0.5-1.0 meter soil/sand cover. The volume flow rate of the pipeline was 29043 m/sup 3/hour at 2kg/cm/sup 2/ pressure. The linear speed of water flowing inside the pipeline was around 2 m/sec. This gave rise to a very high volume fast moving system. Radiotracer technique was used to investigate the problem under investigation. About 50 mCi of /sup 131/I radiotracer, in the form of NaI solution, was injected into the system and radiotracer evolution near suspected leakage point(s) was monitored using radiation detectors (NaI, 2 x 2 inch crystal size). Seven detectors were installed around three teeing off pipes (leakage area) inside the plant building and one at the injection point near the pump outlet. On line data acquisition system was used to acquire the radiotracer data. The leakage water was exiting from the floor just along the pipes carrying main flow of water. The time lag between the arrival, at detectors, of radiotracer flowing inside the pipeline and that present in the leakage water (outside the pipeline) was exploited to identify the position of leakage. The tracer test revealed that there was leakage at two points. The leakage at one point was small as compared at the other points. (author)

Availability note (English)

Available from INIS in electronic form

Files

38039644.pdf

Files (1.5 MB)

Name Size Download all
md5:7d2146580d9910f2789c3e7f5e207ef4
1.5 MB Preview Download

Additional details

Publishing Information

Imprint Pagination
26 p.
Report number
PINSTECH--182