Published September 2012 | Version v1
Journal article

A stochastic simulation model for reliable PV system sizing providing for solar radiation fluctuations

  • 1. Department of Mechanical Engineering, T.E.I. of Patras, Meg. Alexandrou 1, Koukouli 26334, Patra (Greece)

Description

Highlights: ► Solar radiation data for European cities follow the Extreme Value or Weibull distribution. ► Simulation model for the sizing of SAPV systems based on energy balance and stochastic analysis. ► Simulation of PV Generator-Loads-Battery Storage System performance for all months. ► Minimum peak power and battery capacity required for reliable SAPV sizing for various European cities. ► Peak power and battery capacity reduced by more than 30% for operation 95% success rate. -- Abstract: The large fluctuations observed in the daily solar radiation profiles affect highly the reliability of the PV system sizing. Increasing the reliability of the PV system requires higher installed peak power (Pm) and larger battery storage capacity (CL). This leads to increased costs, and makes PV technology less competitive. This research paper presents a new stochastic simulation model for stand-alone PV systems, developed to determine the minimum installed Pm and CL for the PV system to be energy independent. The stochastic simulation model developed, makes use of knowledge acquired from an in-depth statistical analysis of the solar radiation data for the site, and simulates the energy delivered, the excess energy burnt, the load profiles and the state of charge of the battery system for the month the sizing is applied, and the PV system performance for the entire year. The simulation model provides the user with values for the autonomy factor d, simulating PV performance in order to determine the minimum Pm and CL depending on the requirements of the application, i.e. operation with critical or non-critical loads. The model makes use of NASA's Surface meteorology and Solar Energy database for the years 1990–2004 for various cities in Europe with a different climate. The results obtained with this new methodology indicate a substantial reduction in installed peak power and battery capacity, both for critical and non-critical operation, when compared to conventional approaches applied in PV sizing.

Availability note (English)

Available from http://dx.doi.org/10.1016/j.apenergy.2011.12.016

Additional details

Identifiers

DOI
10.1016/j.apenergy.2011.12.016;
PII
S0306-2619(11)00811-7;

Publishing Information

Journal Title
Applied Energy
Journal Volume
97
Journal Page Range
p. 970-981
ISSN
0306-2619
CODEN
APENDX

Conference

Title
3. international conference on applied energy
Dates
16-18 May 2011
Place
Perugia (Italy)

INIS

Optional Information

Copyright
Copyright (c) 2011 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.