Published August 1986 | Version v1
Journal article

Tokamak device TEXTOR: Supplying the high voltage for neutral-beam heating

  • 1. Brown, Boveri und Cie, Turgi (Switzerland). Abt. EKT-TI
  • 2. Kernforschungsanlage Juelich G.m.b.H. (Germany, F.R.)

Description

At the beginning of 1986, two identical high-voltage power supply systems for the two neutral-beam injectors of the TEXTOR tokamak have been accomplished and put into operation by the KFA Juelich. The main new feature of the two systems is a design consisting of 68 non-controlled sources of d.c. voltage, connected in series, which are switched on or off by fast electronic switching instruments. This design allows a current of 100 A to be bzuilt up at an Ohmic load of 550 Ω (corresponding to load voltage of 55 kV) within 20 μs, and switched off within 10 μs. (orig.)

Abstract (German)

Anfang des Jahres 1986 wurden in der Kernforschungsanlage Juelich (KFA) zwei identische Hochspannungsenergieversorgungen fuer die Speisung der beiden Neutralteilcheninjektoren des Fusionsexperimentes TEXTOR errichtet und in Betrieb genommen. Wesentliches neues Merkmal der Versorgung ist der Aufbau aus 68 ungesteuerten, in Serie geschalteten Gleichspannungsquellen, die durch schnelle elektronische Schaltmittel zu- und abgeschaltet werden koennen. Mit diesem Konzept gelingt es, einen Strom von 100 A an einer ohmschen Last von 550 Ω (entsprechend einer Lastspannung von 55 kV) in 20 μs aufzubauen und in 10 μs abzuschalten. (orig.)

Additional details

Additional titles

Original title (German)
Tokamakexperiment TEXTOR: Die Hochspannungsversorgung fuer die Neutralteilchenheizung

Publishing Information

Journal Title
Atomwirtsch., Atomtech.
Journal Volume
31
Journal Issue
8/9
Series
Atomwirtsch., Atomtech.
Journal Page Range
460-462
ISSN
0365-8414
CODEN
AWAKA