Published May 2013 | Version v1
Journal article

A comparison of magnetic fields inside and outside high-voltage urban 110-kV power substations with the exposure recommendations of the Ukrainian regulatory authorities

  • 1. Chair of Power Transmission, Department of Electrical Energy, National Technical University 'Kharkiv Polytechnic Institute', 21, Frunze str., Kharkiv 61002 (Ukraine)
  • 2. Environmental Health, Tampere University of Technology, PO Box 589, Tampere 33101 (Finland)

Description

The aim of this study was to carry out theoretical investigations of power frequency magnetic fields (MFs), produced inside and outside the domain of urban 110-kV power substations and to establish a correspondence between the levels of the fields and the specified population limits as defined by Ukrainian regulations. The fields produced by high-voltage substations were studied based on the application of the numerical finite element methodology. The investigations have shown that magnetic flux density values calculated inside and outside the considered 110-kV power substations do not reach the exposure limits specified by the Ukrainian regulations (1750 μT) and by international guidelines (ICNIRP 2010). Inside the domain of the substation, the maximum value of MFs was found under the 10-kV bus-bars and it equalled 420 μT. (authors)

Availability note (English)

Available from doi: http://dx.doi.org/10.1093/rpd/ncs268

Additional details

Identifiers

Publishing Information

Journal Title
Radiation Protection Dosimetry
Journal Volume
154
Journal Issue
4
Journal Page Range
p. 417-429
ISSN
0144-8420

Optional Information

Notes
31 refs