LOFT pump speed controller stability and accuracy analysis

Description

Two system modifications to the primary coolant pumps motor generators control systems have recently been completed. The range of pump speed operation has been extended and the scoop tube positioner motor replaced. This has necessitated a re-analysis of PSMG stability throughout its range of operation. System accuracy requirements of less than 4 Hz differential pump speed when operating at less than 35 Hz and 8.5 Hz differential pump speed when operating at greater than 35 Hz can be guaranteed by specifying the gain of the system. The installation of the new scoop tube positioner motor will increase the PSMG system's bandwidth and stability. Low speed pump trips should be carefully evaluated if the pump's operational range is to extend to 10 Hz

Availability note (English)

MF available from INIS under the Report Number; Available from NTIS., PC A03/MF A01.