Effect of CRAC units layout on thermal management of data center

Description

Highlights: • CFD study of thermal management in data centers. • Effects of layout arrangements of the CRACs units relative to the racks array on data center performance. • Design guide liens for data centers energy efficiency improvements. - Abstract: Comprehensive numerical studies of thermal management of data centers were presented by several investigators for different geometric and operating conditions of data centers. In the present work, a technical note regarding the effect of the computer room air conditioning (CRAC) units layout arrangements is presented. Two arrangements of CRAC units layouts are investigated; namely locating CRACs units in line with the racks row and locating the CRACs units perpendicular to the rack row. Temperature distributions, air flow characteristics particularly air recirculation and bypass and thermal management in data centers are evaluated in terms of the measureable overall performance parameters: supply/return heat indices (SHI/RHI) and return temperature indices (RTI). The results showed that locating CRAC units perpendicular to the racks row has the following effects: (i) enhances the uniformity of the air flow from the perforated tiles along the rack row, (ii) reduces the hot air recirculation at the ends racks of the row and the cold air bypass at the middle rack of the row and (iii) enhances the data center performance parameters RTI, SHI and RHI.

Availability note (English)

Available from http://dx.doi.org/10.1016/j.applthermaleng.2017.03.003

Additional details

Identifiers

DOI
10.1016/j.applthermaleng.2017.03.003;
PII
S1359-4311(16)33530-X;

Publishing Information

Journal Title
Applied Thermal Engineering
Journal Volume
118
Journal Page Range
p. 339-344
ISSN
1359-4311
CODEN
ATENFT

INIS

Country of Publication
United Kingdom
Country of Input or Organization
International Atomic Energy Agency (IAEA)
INIS RN
48063596
Subject category
S42: ENGINEERING;
Descriptors DEI
AIR CONDITIONING; AIR FLOW; COMPUTERS; ENERGY EFFICIENCY; HEAT; NUMERICAL ANALYSIS; TEMPERATURE DISTRIBUTION
Descriptors DEC
EFFICIENCY; ENERGY; FLUID FLOW; GAS FLOW; MATHEMATICS

Optional Information

Copyright
Copyright (c) 2017 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.