Re-evaluation of the 1995 Hanford Large Scale Drum Fire Test Results
Description
A large-scale drum performance test was conducted at the Hanford Site in June 1995, in which over one hundred (100) 55-gal drums in each of two storage configurations were subjected to severe fuel pool fires. The two storage configurations in the test were pallet storage and rack storage. The description and results of the large-scale drum test at the Hanford Site were reported in WHC-SD-WM-TRP-246, ''Solid Waste Drum Array Fire Performance,'' Rev. 0, 1995. This was one of the main references used to develop the analytical methodology to predict drum failures in WHC-SD-SQA-ANAL-501, 'Fire Protection Guide for Waste Drum Storage Array,'' September 1996. Three drum failure modes were observed from the test reported in WHC-SD-WM-TRP-246. They consisted of seal failure, lid warping, and catastrophic lid ejection. There was no discernible failure criterion that distinguished one failure mode from another. Hence, all three failure modes were treated equally for the purpose of determining the number of failed drums. General observations from the results of the test are as follows: (lgbullet) Trash expulsion was negligible. (lgbullet) Flame impingement was identified as the main cause for failure. (lgbullet) The range of drum temperatures at failure was 600 C to 800 C. This is above the yield strength temperature for steel, approximately 540 C (1,000 F). (lgbullet) The critical heat flux required for failure is above 45 kW/m2. (lgbullet) Fire propagation from one drum to the next was not observed. The statistical evaluation of the test results using, for example, the student's t-distribution, will demonstrate that the failure criteria for TRU waste drums currently employed at nuclear facilities are very conservative relative to the large-scale test results. Hence, the safety analysis utilizing the general criteria described in the five bullets above will lead to a technically robust and defensible product that bounds the potential consequences from postulated fires in TRU waste facilities, the means of storage in which are the Type A, 55-gal drums
Availability note (English)
Available from http://www.llnl.gov/tid/lof/documents/pdf/347148.pdf; PURL: https://www.osti.gov/servlets/purl/908131-6kBLjy/Additional details
Identifiers
Publishing Information
- Imprint Pagination
- 17 p.
- Report number
- UCRL-TR--230686
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 39005479
- Subject category
- S11: NUCLEAR FUEL CYCLE AND FUEL MATERIALS; S12: MANAGEMENT OF RADIOACTIVE WASTES, AND NON-RADIOACTIVE WASTES FROM NUCLEAR FACILITIES; S36: MATERIALS SCIENCE;
- Resource subtype / Literary indicator
- Non-conventional Literature
- Descriptors DEI
- ALPHA-BEARING WASTES; CRITICAL HEAT FLUX; EVALUATION; FLAMES; FUEL STORAGE POOLS; HANFORD RESERVATION; IMPINGEMENT; NUCLEAR FACILITIES; PERFORMANCE; SAFETY ANALYSIS; STORAGE; WASTES; YIELD STRENGTH
- Descriptors DEC
- HEAT FLUX; MATERIALS; MECHANICAL PROPERTIES; NATIONAL ORGANIZATIONS; RADIOACTIVE MATERIALS; RADIOACTIVE WASTES; US DOE; US ERDA; US ORGANIZATIONS; WASTES
Optional Information
- Contract/Grant/Project number
- W-7405-ENG-48
- Notes
- doi 10.2172/908131;PDF-FILE: 17; SIZE: 0.8 MBYTES
- Funding organization
- US Department of Energy (United States)