Description

Redundant measurement, trip, and actuation channels are required for reactor trips and engineered safety systems in nuclear power plants. There are three or four independent channels in existing plants, depending on the system. To prevent failures, consistent signals from any two channels together can trip the reactor or actuate safety systems. Measurements associated with safety trips and actuations include uncertainties related to the instruments making the measurements and to process conditions. Margins that include measurement uncertainties are set for each trip and actuation channel as though it were the only one taking action, thus preserving independence. There are sensors, however, that provide partially redundant information that could be used to decrease the uncertainty associated with measurements of plant conditions, while maintaining the three-channel redundancy important to plant safety. Reducing these uncertainties would both improve plant safety by providing more accurate knowledge of plant conditions and improve the operating margins that must take such uncertainties into account. This paper demonstrates how information that is already available to plant instrumentation and control systems and is already redundant can be used through software routines to reduce the error that must be taken into account in reactor trip and safety system actuation setpoints. Issues that would have to be addressed related to standards, licensing, and implementation are also discussed. (authors)

Additional details

Publishing Information

Publisher
American Nuclear Society - ANS
Imprint Place
La Grange Park, IL (United States)
Imprint Pagination
11 p.

Conference

Title
10. International Conference on Nuclear Plant Instrumentation, Control, and Human-Machine Interface Technologies
Acronym
NPIC and HIMIT 2017
Dates
11-15 Jun 2017
Place
San Francisco, CA (United States)

Optional Information

Notes
7 refs.; available from American Nuclear Society - ANS, 555 North Kensington Avenue, La Grange Park, IL 60526 (US)