This report presents an experimental evaluation of the effects of water fog density, droplet diameter, and temperature on the lower flammable limit (LFL) of hydrogen-air-steam mixtures. The results show that the LFL for hydrogen in air at 200C is only marginally higher with fog than without. Most of the nozzles tested at 200C raised the hydrogen LFL from 4.0 vol % to about 4.8%, for the case of dense fogs with volume-average drop size in the range 45 to 90 microns. The lower flammable limit at 500C was typically 7.2% for dense fogs with drop size in the range 25 to 50 microns. The lower flammable limit at 700C was typically 7.6%. Typical fog concentrations ranged from 0.03 to 0.09 vol % at 200C and decreased with increasing fog temperature. 7 figures, 4 tables
Availability note (English)
MF available from INIS under the Report Number; Available from NTIS, PC A05/MF A01 as DE83900639.
Files
Additional details
Publishing Information
- Imprint Pagination
- 81 p.
- Report number
- EPRI-NP--2637
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 14754995
- Subject category
- S61: RADIATION PROTECTION AND DOSIMETRY;
- Resource subtype / Literary indicator
- Numerical Data
- Descriptors DEI
- ATMOSPHERIC PRECIPITATIONS; BENCH-SCALE EXPERIMENTS; COMBUSTION; CONTAINMENT BUILDINGS; CONTROLLED ATMOSPHERES; DENSITY; DROPLETS; EXPERIMENTAL DATA; FLAMMABILITY; HYDROGEN; WATER VAPOR
- Descriptors DEC
- CHEMICAL REACTIONS; CONTAINMENT; DATA; ELEMENTS; FLUIDS; GASES; INFORMATION; NONMETALS; NUMERICAL DATA; OXIDATION; PARTICLES; PHYSICAL PROPERTIES; VAPORS