Published 1986 | Version v1
Book

Failure of welded pipe in the cooling system of a nuclear reactor

  • 1. Nuclear Research Centre - Negev

Description

Routine inspection of the cooling system of a nuclear reactor at the Nuclear Research Centre-Negev in Israel detected serious leaks of heavy water in both the inlet and outlet pipes of the primary coolant heat exchangers. After disassembly, the heat exchanger was submitted to a series of nondestructive tests, which included ultrasonic, dye penetrant, and radiographic inspections. A flawed part was found, removed, mechanically tested, and examined. The cracked areas of the Inconel 600/sup 2/ tube were studied using optical and scanning electron microscopy. Chemical analyses of both cracked and intact tubes were carried out. Stress-corrosion cracking was determined to be the main mode of failure; minor evidence of fatigue was also encountered. This paper describes the investigation that determined the cause and location of the cracks and suggest measures to prevent their reoccurrence

Additional details

Publishing Information

Publisher
American Nuclear Society.
Imprint Place
La Grange Park, IL (USA)
Imprint Title
Proceedings of the 1986 joint ASME/ANS nuclear power conference
Journal Page Range
p. 548-551.

Conference

Title
safe and reliable nuclear power plants.
Acronym
ASME/ANS bi-annual nuclear power conference
Dates
20-23 Jul 1986.
Place
Philadelphia, PA (USA).