Numerical investigation for optimizing segmented micro-channel heat sink by Taguchi-Grey method
Creators
- 1. Lee Kong Chian Faculty of Engineering and Science, UTAR, Kajang 43000 (Malaysia)
- 2. Department of Mechanical Engineering, Faculty of Engineering, University of Malaya, 50603 (Malaysia)
- 3. School of Engineering and The Built Environment, Edinburgh Napier University, Edinburgh EH10 5DT (United Kingdom)
Description
Highlights: • Novel segmented micro-channel heat sink has been designed. • CFD models have been developed to simulate the performance of the segmented micro-channel. • Enhanced the cooling performance of the straight micro-channel. • Optimizing the segmented micro-channel using Taguchi-Grey method. • Optimized design parameters for segmented micro-channel have been identified. The scale-down trend increases the chips' density and the high power handling capability generates unnecessary heat which can disrupt the reliability of the electronic devices. Therefore, various types of cooling solution have been proposed to enhance heat dissipation from the electronic devices. One of the solution is using inexpensive straight-channel heat sink. However, the presence of large temperature gradient between the upstream and downstream in the straight-channel can shorten the life span of the device and subsequently reduce the reliability. In this study, a novel segmented micro-channel is introduced to improve the thermal performance of the straight-channel heat sink. Computational fluid dynamic analysis are performed to investigate the performance of the micro-channel heat sink. The bottom of the heat sink is subjected to a constant heat flux condition and water is used as a coolant. Following that, Taguchi-grey method is applied to optimize the design of the segmented micro-channel. The effect of fin width, fin length, fin transverse distance, number of segments, channel width and mass flow rate on the specific performance, variation of temperature and pressure drop are investigated. The results indicate that a three segments of segmented micro-channel, fin width-1 mm, fin length-2 mm, fin transverse distance-5 mm and channel width-1 mm have successfully enhance the heat transfer performance with minimum pressure drop. It is also found that the optimized micro-channel heat sink is able to cool the chip with heat flux of 800 W to 56.6 °C and pumping power of 0.13 W using 15 gs−1 of water.
Availability note (English)
Available from http://dx.doi.org/10.1016/j.apenergy.2018.03.186Additional details
Identifiers
- DOI
- 10.1016/j.apenergy.2018.03.186;
- PII
- S0306261918305336;
Publishing Information
- Journal Title
- Applied Energy
- Journal Volume
- 222
- Journal Page Range
- p. 437-450
- ISSN
- 0306-2619
- CODEN
- APENDX
INIS
- Country of Publication
- United Kingdom
- Country of Input or Organization
- International Atomic Energy Agency (IAEA)
- INIS RN
- 52106887
- Subject category
- S42: ENGINEERING;
- Descriptors DEI
- COMPUTERIZED SIMULATION; COOLANTS; COOLING; ELECTRONIC EQUIPMENT; ENERGY LOSSES; FLOW RATE; FLUID MECHANICS; HEAT FLUX; HEAT SINKS; HEAT TRANSFER; OPTIMIZATION; PRESSURE DROP; RELIABILITY; TEMPERATURE GRADIENTS; THERMAL DIFFUSIVITY; THERMAL EFFLUENTS; WATER
- Descriptors DEC
- ENERGY TRANSFER; EQUIPMENT; HYDROGEN COMPOUNDS; LOSSES; MECHANICS; OXYGEN COMPOUNDS; PHYSICAL PROPERTIES; SIMULATION; SINKS; THERMODYNAMIC PROPERTIES
Optional Information
- Copyright