Mixing systems for wet and dry plumes and cleaning equipment for the heat exchangers of the dry section. Two indispensible components of an effective and safe hybrid cooling tower

Creators

Description

At first glance, the hybrid cooling tower seems to be an ingenious combination of the well known components of an evaporative cooling tower and a dry cooling tower. The calculation of the air mass flows for both the wet and dry sections required to achieve an invisible plume does not represent an unsolvable problem to the engineer experienced in thermodynamics. The same also applies to the dimensioning of the heat exchangers and cooling fills. The hybrid cooling tower requires a well designed mixing system in order to ideally mix, the dry plume into the wet plume. If the cooling tower proves its efficiency during commissioning it is important that the ratio of the performance of the wet section to that of the dry section be maintained also in the long term. The performance of the fill in a wet cooling tower is consistently stable. Dirt deposits can form very quickly on the inner and outer surfaces of the heat exchangers of the dry section. In this case the thermal resistance increases rapidly. The respective performance of the wet and dry sections is then no longer balanced and the invisibility of the plume is no longer assured. This can be avoided by providing appropriate cleaning equipment

Additional details

Publishing Information

Imprint Title
International cooling-tower and spray pond symposium. Proceedings
Imprint Pagination
605 p.
Journal Page Range
p. D3.1-D3.9.
Report number
EPRI-GS--6976

Conference

Title
7. international association for hydraulic research cooling tower and spraying pond symposium.
Dates
29 May - 2 Jun 1990.
Place
Leningrad (USSR).

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
23008509
Subject category
S22: GENERAL STUDIES OF NUCLEAR REACTORS;
Resource subtype / Literary indicator
Conference, Non-conventional Literature
Descriptors DEI
COLUMN PACKING; COOLING TOWERS; FEDERAL REPUBLIC OF GERMANY; HEAT EXCHANGERS; HEAT TRANSFER; MAINTENANCE; PERFORMANCE; SPECIFICATIONS; SURFACE CLEANING; THERMAL EFFICIENCY
Descriptors DEC
CLEANING; DEVELOPED COUNTRIES; EFFICIENCY; ENERGY TRANSFER; EUROPE; SURFACE FINISHING