MARS Simulation of Air Cooling Heat Exchanger Connected with PAFS
- 1. FNC Technology Co., Yongin (Korea, Republic of)
- 2. Korea Atomic Energy Research Institute, Daejeon (Korea, Republic of)
Description
Current working time of PAFS cannot meet the required 72 hours cooling capability for the long term Station Black-Out (SBO) situation. Therefore, it is required to improve the design of PAFS for the long term cooling. In order to ensure the long term cooling of PAFS, the heat exchanger tube should be submerged in the water of the PAFS pool. It can be achieved by condensing the steam vented from the PAFS pool. The Air Cooling Heat Exchanger (ACHX) is installed above the PAFS pool. It is expected that the ACHX condenses the steam vented from the PAFS pool and delays the depletion time of the water in the PCCT. Therefore, this paper introduces the MARS-KS1.4 modeling of the ACHX and the performance analysis results on the PAFS connected with the ACHX. For the long term cooling with PAFS, KAERI proposed a new passive air-water combined cooling system. In this study, the modeling of the ACHX and the performance analysis on the PAFS connected with the ACHX were carried out with MARS. MARS predicted the behavior of main thermal-hydraulic variables of ACHX reasonably. Then, it was found that the long term cooling of PAFS could be achieved by the installation of the ACHX in which the tube length is 6 m and the number of tubes is 8000
Additional details
Publishing Information
- Publisher
- KNS
- Imprint Place
- Daejeon (Korea, Republic of)
- Imprint Title
- Proceedings of the KNS 2016 Autumn Meeting
- Imprint Pagination
- [1 CD-ROM]
- Journal Page Range
- [2 p.]
Conference
- Title
- 2016 Autumn Meeting of the KNS
- Dates
- 26-28 Oct 2016
- Place
- Kyungju (Korea, Republic of)
INIS
- Country of Publication
- Korea, Republic of
- Country of Input or Organization
- Korea, Republic of
- INIS RN
- 48067373
- Subject category
- S22: GENERAL STUDIES OF NUCLEAR REACTORS;
- Resource subtype / Literary indicator
- Conference, Non-conventional Literature
- Descriptors DEI
- COMPUTERIZED SIMULATION; COOLING; DESIGN; HEAT EXCHANGERS; M CODES; PERFORMANCE; TUBES
- Descriptors DEC
- COMPUTER CODES; SIMULATION
Optional Information
- Notes
- 2 refs, 9 figs