Published 1984 | Version v1
Book

TRAC analysis of the Crystal River Unit-3 plant transient of February 26, 1980

  • 1. Los Alamos National Lab., Los Alamos, NM

Description

This paper describes the application of the TRAC-PD2 and TRAC-PF1 codes to analyze the Crystal River transient. The PD2 and PF1 analyses used the three-dimensional and one-dimensional vessel models, respectively. Both calculations predicted the plant depressurization caused by the open PORV and the subsequent repressurization caused by closing the PORV and continuing highpressure injection flow. Also, natural circulation was calculated in loop B following reestablishment of feedwater to the loop-B steam generator. After system repressurization, the codes calculated that pressure was relieved through the safety valves, and an intermittent flow occurred in loop A because of high-pressure-injection-driven density variations

Additional details

Publishing Information

Publisher
Plenum Press.
Imprint Place
New York, NY (USA)
Imprint Title
Anticipated and abnormal plant transients in light water reactors, Vol. 1
Journal Page Range
p. 527-538.

Conference

Title
Anticipated and abnormal plant transients in light water reactors conference.
Dates
26-29 Sep 1983.
Place