Published 1999
| Version v1
Journal article
Determination of air exchange rates of rooms and deposition factors for fine particles by means of photoelectric aerosol sensors
Creators
- 1. Federal Institute of Technology (ETH), Solid State Physics, Zurich (Switzerland)
- 2. Eidgenoessische Materialpruefungs- und Forschungsanstalt, Duebendorf (Switzerland)
Description
Indoor and outdoor concentrations or airborne fine particles from internal combustion engines have been measured over periods of 24 h with a time resolution of 10 s. With this time series, the ventilation air exchange rate of different rooms has been computed using a novel approach to the solution of the mass balance equation. A 'mixing time' parameter has been introduced in order to account for the initial non-homogeneous distribution of the pollutants in the rooms. It is demonstrated that this method can be used to determine the impact of health relevant outdoor particles on the indoor particle concentration. This yields information on the protection a building offers against pollutants entering from outdoors. (author)
Additional details
Publishing Information
- Journal Title
- Indoor and Built Environment
- Journal Volume
- 8
- Journal Issue
- 4
- Series
- figs., tabs., refs.
- Journal Page Range
- p. 246-254
- ISSN
- 1420-326X
INIS
- Country of Publication
- Switzerland
- Country of Input or Organization
- Switzerland
- INIS RN
- 33026706
- Subject category
- S54: ENVIRONMENTAL SCIENCES; S61: RADIATION PROTECTION AND DOSIMETRY;
- Resource subtype / Literary indicator
- Numerical Data
- Descriptors DEI
- AIR POLLUTION; AIR POLLUTION MONITORING; BUILDINGS; CALCULATION METHODS; COMPUTERIZED SIMULATION; EXPERIMENTAL DATA; INDOOR AIR POLLUTION; PARTICULATES; PUBLIC HEALTH; SAFETY; VENTILATION
- Descriptors DEC
- AIR POLLUTION; DATA; INFORMATION; MONITORING; NUMERICAL DATA; PARTICLES; POLLUTION; SIMULATION