Published July 1987 | Version v1
Journal article

Radon daughter considerations in a nuclear power plant

Description

A boiling water reactor in the start-up phase experienced a significant number of personnel contamination monitor alarms caused by radon daughter plateout on hard hats, clothing, and shoes. Alarm frequencies were compared to environmental conditions and ventilation system operations to determine the effects of various factors on radon plateout. High normal ventilation, radon daughter concentrations in the plant were found to be similar to outdoor concentrations, and alarm frequencies were inversely related to relative humidity. When ventilation systems were shutdown, indoor radon levels and personnel contamination monitor alarm rates increased significantly. In this paper some suggestions for accounting for radon daughter contamination in monitoring and training programs are presented

Additional details

Publishing Information

Journal Title
Radiation Protection Management
Journal Volume
4
Journal Issue
4
Series
Radiat. Prot. Manage.
Journal Page Range
52-58
ISSN
0740-0640