Published October 1977
| Version v1
Report
Restricted
Experiments with vacuum interrupters used for large dc-current interruption
Description
Vacuum interrupters have been tested in circuits similar to those used in theta-pinch and Tokamak fusion devices. The effects on performance of auxiliary circuit components and axial magnetic fields have been determined, and limits to lifetime caused by mechanical and electrical wear have been measured. Results show that the upper reliable limit of interruption is independent of the auxiliary components but quite dependent on interrupter size and on the axial field
Availability note (English)
MF available from INIS under the Report Number; Available from NTIS., PC A02/MF A01.
Files
Additional details
Publishing Information
- Imprint Pagination
- 24 p.
- Report number
- LA--6909-MS
INIS
- Country of Publication
- United States
- Country of Input or Organization
- United States
- INIS RN
- 9381111
- Subject category
- S70: PLASMA PHYSICS AND FUSION TECHNOLOGY;
- Descriptors DEI
- DIRECT CURRENT; ELECTRONIC CIRCUITS; LINEAR THETA PINCH DEVICES; PERFORMANCE; RELIABILITY; SWITCHES; THERMONUCLEAR REACTORS; TOKAMAK DEVICES
- Descriptors DEC
- CLOSED PLASMA DEVICES; CURRENTS; ELECTRIC CURRENTS; ELECTRICAL EQUIPMENT; LINEAR PINCH DEVICES; OPEN PLASMA DEVICES; PINCH DEVICES; THERMONUCLEAR DEVICES