Corrosion Resistance of Zn and Cu Coated Steel Pipes as a Substitute for Cu Pipe in an Air Conditioner System

  • 1. Chonnam National University, Gwangju (Korea, Republic of)

Description

We investigated the corrosion resistance of Zn and Cu coated steel pipes as a substitute for Cu pipe in an air-conditioner system. In addition, the galvanic corrosion tendency between two dissimilar metal parts was studied. The corrosion resistance of the Cu electroplated steel was similar to that of Cu, while the corrosion rate of the Zn electro-galvanized and the galvalume (Zn-55 % Al) coated steels was much higher and not suitable for Cu substitute in artificial sea water and acidic rain environments. Furthermore, the galvanic difference between Cu electroplated steel and Cu was so small that the Cu coated steel pipe can be used as a substitute for Cu pipe in an air-conditioner system

Additional details

Publishing Information

Journal Title
Corrosion Science and Technology
Journal Volume
8
Journal Issue
1
Series
8 refs, 4 figs
Journal Page Range
p. 40-43
ISSN
1598-6462

INIS

Country of Publication
Korea, Republic of
Country of Input or Organization
Korea, Republic of
INIS RN
43125294
Subject category
S36: MATERIALS SCIENCE;
Descriptors DEI
AIR CONDITIONERS; COPPER; CORROSION RESISTANCE; PIPES; SEAWATER; ZINC
Descriptors DEC
ELEMENTS; HYDROGEN COMPOUNDS; METALS; OXYGEN COMPOUNDS; TRANSITION ELEMENTS; TUBES; WATER