An automatic 3 MeV variation of a 30 MeV A-beam was performed in 300 steps at the Bonn Isochronous Cyclotron. A microcomputer in connection with a control unit adjusted the cyclotron and the monochromator system parameters. This combination allowed a direct and precise measurement of broad excitation functions. Using fast magnetic field stabilization an energy-shift was accomplished to an accuracy of better than 1 part in 105 within 20 s. The stability of the beam position on the target was about 0.05 mm. (Auth.)
Additional details
Publishing Information
- Journal Title
- Nucl. Instrum. Methods
- Journal Volume
- 157
- Journal Issue
- 2
- Series
- Nucl. Instrum. Methods.
- Journal Page Range
- 311-314
- ISSN
- 0029-554X
INIS
- Country of Publication
- Netherlands
- Country of Input or Organization
- Netherlands
- INIS RN
- 10452587
- Subject category
- S43: PARTICLE ACCELERATORS;
- Descriptors DEI
- ACCURACY; EXCITATION FUNCTIONS; HELIUM 4 BEAMS; ISOCHRONOUS CYCLOTRONS; MAGNETIC FIELDS; MEV RANGE 10-100; MICROPROCESSORS; MONOCHROMATORS; ON-LINE CONTROL SYSTEMS; ON-LINE MEASUREMENT SYSTEMS; STABILITY
- Descriptors DEC
- ACCELERATORS; BEAMS; COMPUTERS; CONTROL SYSTEMS; CYCLIC ACCELERATORS; CYCLOTRONS; ENERGY RANGE; ION BEAMS; MEV RANGE; ON-LINE SYSTEMS