Risk due to internal flooding has been one of the major concerns for the design and operation of nuclear power plants. To reduce the risk from internal flooding, two design approaches for flood protection systems, active and passive, can be considered. The approaches to flood protection design are different for each plant design, and they are highly dependent on the plant type. The flood PSA revealed that the potential plant risk due to a flooding event is highly dependent on the flood design. The major design characteristics are 1) the location of systems that utilize sea water and their impact to other safety related systems, and 2) the existence of emergency overflow paths and an emergency sump which can transfer and accommodate flood water to prevent a significant flooding event. To identify and compare the effectiveness and potential vulnerability of various Korean nuclear power plants' flood designs, the flood PSAs have been performed for three plant designs, such as existing Korean PWR plants, CANDU type PHWR plants, and Korean Standard Nuclear Plants. Based on the evaluation, several design changes were recommended. (author)

Availability note (English)

Available from Canadian Nuclear Society, 144 Front Street, Suite 475, Toronto, ON M5J 2L7, Canada
Part of:
Proceedings of the 11th Pacific Basin Nuclear Conference

Additional details

Publishing Information

Publisher
Canadian Nuclear Society
Imprint Place
Toronto, ON (Canada)
ISBN
0-919784-57-7
Imprint Title
Proceedings of the 11th Pacific Basin Nuclear Conference
Imprint Pagination
2 v.
Journal Page Range
v. 2 p. 1437-1444

Conference

Title
11. Pacific Basin Nuclear Conference. International Co-operation in the Pacific Rim for the 21st Century
Dates
3-7 May 1998
Place
Banff, Alberta (Canada)

Optional Information

Notes
5 refs., 1 tab.