Published 2008 | Version v1
Book

Studies on the cause of damage and measures against small leaks in Elbe water charged cooling water systems

Creators

  • 1. Westinghouse Electric Germany GmbH, Mannheim (Germany)

Description

During the operational duty cycle 2005/2006 tubing of auxiliary cooling water systems in a German NPP experienced leakages that were caused by corrosive attacks of the Elbe water. Extensive investigations included the safety relevant consequences, clarification of the cause of damage and measures concerning repair and prevention in the future including an improved test program. The study revealed local pitting corrosion that started as subsurface corrosion. There was no risk for flooding. Material investigations showed that the used coating scheme for long-term protection at the inside of the piping is appropriate with respect to the cooling water. Concerning aging the important properties of the coating have not changed over the operational time. During the revision in 2006 extensive visual inspection of the piping inner wall was performed, defects were repaired.

Part of:
Annual meeting on nuclear technology 2008. Proceedings

Additional details

Additional titles

Original title (German)
Untersuchungen zur Schadensursache und Massnahmen gegen Kleinleckagen in elbwasserbeaufschlagten Kuehlwassersystemen

Publishing Information

Publisher
Inforum Verlag
Imprint Place
Bonn (Germany)
Imprint Title
Annual meeting on nuclear technology 2008. Proceedings
Imprint Pagination
886 p.
Journal Page Range
p. 539-542

Conference

Title
2008 annual meeting on nuclear technology
Original Conference Title
Jahrestagung Kerntechnik (JK) 2008
Dates
27-29 May 2008
Place
Hamburg (Germany)

Optional Information

Notes
Imprint:Jahrestagung Kerntechnik 2008. Tagungsbericht