Description

Serviceability of the accident heat removal system from containment shell of NPP is investigated. Results of experimenters with the model of the system are presented. Regimes of unstable operation of the heat removal system because of rise of hydraulic hammers and vibration of the equipment were detected. Reasons of these events were determined. It is noted that instability of the operation of the system is connected with infiltrate of relatively cold coolant from tank-cooler in overflow pipeline

Abstract (Russian)

Исследуется работоспособность системы аварийного отвода тепла от защитной оболочки АЭС. Представлены результаты экспериментов с моделью данной системы. Обнаружены режимы неустойчивой работы системы отвода тепла, связанные с возникновением гидроударов и вибраций оборудования. Определены причины этих явлений. Отмечается, что неустойчивость работы системы связана с проникновением относительно холодного теплоносителя из бака-охладителя в сбросной трубопровод

Additional details

Additional titles

Original title (Russian)
Стратифицированные одно- и двухфазные течения в горизонтальных трубах и системах труба-емкость

Publishing Information

Journal Title
Atomnaya Ehnergiya
Journal Volume
95
Journal Issue
2
Journal Page Range
p. 98-102
ISSN
0004-7163
CODEN
AENGAB

Optional Information

Notes
2 refs., 5 figs., 2 tabs.