Published 1994 | Version v1
Report Open

Hanford gas dispersion analysis

Description

An analysis was performed to verify the design of a waste gas exhauster for use in support of rotary core sampling activities at the Westinghouse Hanford Waste Tank Farm. The exhauster was designed to remove waste gases from waste storage tanks during the rotary core drilling process of the solid materials in the tank. Some of the waste gases potentially are very hazardous and must be monitored during the exhauster's operation. If the toxic gas concentrations in specific areas near the exhauster exceed minimum Threshold Limit Values (TLVs), personnel must be excluded from the area. The exhauster stack height is of interest because an increase in stack height will alter the gas concentrations at the critical locations. The exhaust stack is currently ∼4.6 m (15 ft) high. An equipment operator will be located within a 6.1 m (20 ft) radius of the exhaust stack, and his/her head will be at an elevation 3.7 m (12 ft) above ground level (AGL). Therefore, the maximum exhaust gas concentrations at this location must be below the TLV for the toxic gases. Also, the gas concentrations must be within the TLV at a 61 m (200 ft) radius from the stack. If the calculated gas concentrations are above the TLV, where the operator is working below the stack at the 61 m (200 ft) radius location, the stack height may need to be increased

Availability note (English)

MF available from INIS under the Report Number; Also available from OSTI as DE94014294; NTIS; US Govt. Printing Office Dep.

Files

26017423.pdf

Files (1.2 MB)

Name Size Download all
md5:0f8de7e071af9e8e34e1dfee55e34c3d
1.2 MB Preview Download

Additional details

Publishing Information

Imprint Pagination
13 p.
Report number
LA-UR--94-2017

Conference

Title
Winter meeting of the American Nuclear Society.
Dates
13-18 Nov 1994.
Place
Washington, DC (United States).

Optional Information

Contract/Grant/Project number
Contract W-7405-ENG-36
Funding organization
USDOE, Washington, DC (United States).
Secondary number(s)
CONF-941102--4.