Evaluation of electrical power quality of LVMDB2 panels at radioactive waste technology center

  • 1. Pusat Teknologi Limbah Radioaktif - BATAN, Kawasan Puspiptek Gedung 50, Serpong, Tangerang Selatan (Indonesia)

Description

The Low Voltage Main Distribution Board 2 (LVMDB2) electric panel is one of the electrical systems at the Center for Radioactive Waste Technology which functions to supply electrical power to sewage treatment plant equipment, supporting facilities, and office rooms. The quality of electrical power must always be maintained so that the equipment it supplies is not damaged quickly. One of the power quality parameters that need to be watched is the harmonic value. Harmonics are disturbances that occur in the electric power distribution system due to current and voltage wave distortions. To assess the quality of this electric power it is necessary Evaluation activities are carried out. Activities are aimed at obtaining recommendations for action, if there has been a deviation from the set standard value. The method used is to compare the data from the measurement of system operating parameters with the values in the Institute of Electrical and Electronic Engineers (IEEE) standard. Measurement of electric power parameters using the Power Factor Controller BR 6000 module. This activity has concluded that the quality of the power factor/cos ϴ is 0.97-0.98. The amount of voltage harmonic distortion (% THDV) of the LVMDB2 panel is in the range 1.1 to 2.5 %, and current harmonic distortion (% THDI) is in the range of 5.0 to 7.6 %. The value of voltage and current harmonic distortion compared to the IEEE 519-2014 standard is below the maximum limit of harmonic distortion. The maximum limit of voltage harmonic distortion is 5 % and the maximum limit of harmonic distortion of electric current is 15 %. (author)

Files

54113013.pdf

Files (725.9 kB)

Name Size Download all
md5:68f4f918b5f30dfb3cf4902017f35f13
725.9 kB Preview Download
Part of:
Proceedings of Research Results and Activities of the Center for Radioactive Waste Technology in 2020

Additional details

Additional titles

Original title (Indonesian)
Evaluasi kualitas daya listrik panel LVMDB2 di pusat tekologi limbah radioaktif

Publishing Information

Publisher
Center for Radioactive Waste Technology, National Nuclear Energy Agency
Imprint Place
Tangerang Selatan (Indonesia)
Imprint Title
Proceedings of Research Results and Activities of the Center for Radioactive Waste Technology in 2020
Imprint Pagination
272 p.
Journal Page Range
p. 159-166
ISSN
0852-2979
Report number
INIS-ID--110

Conference

Title
Results of Research and Activities of the Center for Radioactive Waste Technology in 2020
Original Conference Title
Hasil Penelitian dan Kegiatan Pusat Teknologi Limbah Radioaktif (PTLR) tahun 2020
Dates
20-21 Apr 2021
Place
Tangerang Selatan (Indonesia)

INIS

Country of Publication
Indonesia
Country of Input or Organization
Indonesia
INIS RN
54113013
Subject category
S29: ENERGY PLANNING, POLICY AND ECONOMY;
Resource subtype / Literary indicator
Conference
Descriptors DEI
CONTROL ROOMS; ELECTRIC CONTROLLERS; ELECTRIC POWER; ELECTRICAL EQUIPMENT; ELECTRICITY; PANELS; POWER; POWER SYSTEMS; SEWAGE; VOLTAGE REGULATORS
Descriptors DEC
CONTROL EQUIPMENT; ENERGY SYSTEMS; EQUIPMENT; POWER; WASTES

Optional Information

Notes
6 refs.; 5 tabs.; 5 figs. Imprint:Prosiding Hasil Penelitian dan Kegiatan Pusat Teknologi Limbah Radioaktif (PTLR) tahun 2020