Development of protection system for power supply facilities in JT-60U P-NBI for long pulse operation
Creators
- 1. Japan Atomic Energy Agency, Fusion Research and Development Directorate, Naka, Ibaraki (Japan)
Description
In the positive ion based NBI (P-NBI) system, we have developed a protection system to protect the power supply facilities from over load during long pulse operation. The protection system monitors the voltage (V) and current (I) in the power supply facilities, and calculates the parameters of V2t and I2t in real-time, where T is the pulse duration. It turns off the power supply facilities when V2t and I2t are beyond the critical values. After two development stages, we have completed the protection system using a package typed PLC (Programmable Logic Controller) which has a high expandability of multi-unit operation. Moreover, we have constructed a user-friendly system by using a SCADA (Supervisory Control and Data Acquisition) system. (author)
Availability note (English)
Available from JAEA; DOI: https://doi.org/10.11484/jaea-technology-2007-044
Files
System files
(37.8 kB)
| Name | Size | Download all |
|---|
Additional details
Identifiers
Publishing Information
- Imprint Pagination
- 36 p.
- Report number
- JAEA-Technology--2007-044
INIS
- Country of Publication
- Japan
- Country of Input or Organization
- Japan
- INIS RN
- 39072900
- Subject category
- S70: PLASMA PHYSICS AND FUSION TECHNOLOGY;
- Descriptors DEI
- CONTROL SYSTEMS; JT-60U TOKAMAK; MATHEMATICAL LOGIC; MONITORING; NEUTRAL ATOM BEAM INJECTION; NUCLEAR FACILITIES; POWER SUPPLIES; PROGRAMMING; PULSES; REACTOR OPERATION; REACTOR PROTECTION SYSTEMS; SAFETY
- Descriptors DEC
- BEAM INJECTION; CLOSED PLASMA DEVICES; ELECTRONIC EQUIPMENT; ENGINEERED SAFETY SYSTEMS; EQUIPMENT; OPERATION; THERMONUCLEAR DEVICES; TOKAMAK DEVICES
Optional Information
- Notes
- 4 refs., 10 figs., 3 tabs.; This record replaces 39021881