Published December 2006
| Version v1
Journal article
Applied study of coordinate control of nuclear-power system
Creators
- 1. Harbin Engineering Univ., Harbin (China). School of Power and Nuclear Engineering
Description
On the basis of traditional PID controller, coordinate controller is introduced, which formed the control system of nuclear power plant. The control system is applied to the nuclear power plant and processed simulation experiment. The simulation results show that the overshoot of the primary water's average temperature and exit steam' pressure after applying the coordinate control system is smaller than that of the traditional PID control system. The steady time is shortened, while the rise time of turbine power is a little longer. But the peaking overshoot turns smaller. (authors)
Additional details
Publishing Information
- Journal Title
- Chinese Journal of Nuclear Science and Engineering
- Journal Volume
- 26
- Journal Issue
- 4
- Journal Page Range
- p. 337-342
- ISSN
- 0258-0918
INIS
- Country of Publication
- China
- Country of Input or Organization
- China
- INIS RN
- 38093643
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Descriptors DEI
- CONTROL SYSTEMS; DESIGN; MATHEMATICAL MODELS; MODIFICATIONS; NUCLEAR POWER PLANTS; REACTORS; SIMULATION; STEAM GENERATORS; TURBINES
- Descriptors DEC
- BOILERS; EQUIPMENT; MACHINERY; NUCLEAR FACILITIES; POWER PLANTS; THERMAL POWER PLANTS; TURBOMACHINERY; VAPOR GENERATORS
Optional Information
- Notes
- 4 figs., 4 refs.