Published October 2009 | Version v1
Journal article

Experimental investigation on a solid desiccant system integrated with a R407C compression air conditioner

  • 1. Department of Mechanical Power Engineering, Faculty of Engineering, El-Mattaria (Helwan University), Masaken El-Helmia P.O., Cairo 11718 (Egypt)
  • 2. King Saud University, P.O. 70908, 11577 Riyadh (Saudi Arabia)

Description

In the present work, experimental performance data of a solid desiccant based hybrid air conditioning system are presented. The system consists of a packed bed solid desiccant integrated with a R407C conventional vapor compression refrigeration system. Experiments are carried out during dehumidification operation mode for various operating parameters such as; desiccant mass on shelves (5, 10 and 15 kg), air mass flow rate (7.4 and 10.2 kg/min), shelves number (1, 2 and 3) and three values of shelves span (7, 14 and 28 cm) at evaporator air inlet conditions of 28 deg. C DBT and 66% RH, condenser air inlet volume flow rate of 850 m3/h and temperature of 35 deg. C. The reactivation of the desiccant at different regeneration temperatures and air flow rates as well as desiccant masses is also investigated. During the dehumidification mode, the average system coefficient of performance increases by 6.2% and 1.61% when the mass of desiccant increases from 5 to 10 kg and from 10 to 15 kg, respectively. The enhancement in the coefficient of performance is 6.2% due to increasing the air mass flow rate from 7.4 to 10.2 kg/min. Increasing both shelves number and span yields to a reduction in the adsorption rate that can be extracted by the desiccant material in the ranges of considered operating conditions. The regeneration temperature and the air flow rate of regeneration have significant effects on the reactivation process. It was found that, with increasing the mass flow rate of regenerated air from 7.4 to 10.2 kg/min produces a reduction in regeneration time by 87.5% and an augmentation in the desorption rate by 16% after 10 min of regeneration. In addition, with escalating the regeneration temperature from 45 to 55 deg. C, the reactivation time reduces by 25%. Reported results revealed that solid desiccant based hybrid air conditioning system reduces the compressor electric power and the number of electric unit (kW h) by 10.2%.

Availability note (English)

Available from http://dx.doi.org/10.1016/j.enconman.2009.06.020

Additional details

Identifiers

DOI
10.1016/j.enconman.2009.06.020;
PII
S0196-8904(09)00239-8;

Publishing Information

Journal Title
Energy Conversion and Management
Journal Volume
50
Journal Issue
10
Journal Page Range
p. 2670-2679
ISSN
0196-8904
CODEN
ECMADL

INIS

Country of Publication
United Kingdom
Country of Input or Organization
International Atomic Energy Agency (IAEA)
INIS RN
41058213
Subject category
S29: ENERGY PLANNING, POLICY AND ECONOMY;
Descriptors DEI
ADSORPTION; AIR CONDITIONERS; AIR CONDITIONING; AIR FLOW; AUGMENTATION; COEFFICIENT OF PERFORMANCE; COMPRESSION; COMPRESSORS; DESICCANTS; DESORPTION; DRYING; ELECTRIC POWER; FLOW RATE; MASS; PACKED BEDS; REFRIGERATION; REGENERATION; SOLIDS; VAPORS; YIELDS
Descriptors DEC
COOLING; FLUID FLOW; FLUIDS; GAS FLOW; GASES; POWER; SORPTION

Optional Information

Copyright
Copyright (c) 2009 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.