Published May 2001 | Version v1
Miscellaneous

Integrity evaluation of ice plugging of short pipes

  • 1. Korea Hydro and Nuclear Power Co., LTD, Pusan (Korea, Republic of)
  • 2. Busan National Univ., Pusan (Korea, Republic of)

Description

In many special industiral fields such as nuclear power plants and chemical plants, it is often necessary to repair internal leaking pipe with hazardous or expensive fluid. A ice plugging by blocking an internal flow is considered as a useful method in that case. According to the pipe freezing guideline of nuclear power plant, the length of a freezing jacket must be longer than twice of the pipe diameter. However, for applying the ice plugging to short pipes which do not have enough freezing length, it is inevitable to use shorter jacket less than twice of the pipe diameter. In this study, the integrity evaluation for short pipes in the nuclear power plant is conducted by the finite element analysis. From the result, the ice plugging process in the short pipes can be safety carried out without any plastic deformation and fracture

Part of:
Proceedings of the Korean Nuclear Society spring meeting

Additional details

Publishing Information

Publisher
KNS
Imprint Place
Taejon (Korea, Republic of)
Imprint Title
Proceedings of the Korean Nuclear Society spring meeting
Imprint Pagination
[ONE CDROM]
Journal Page Range
[12 p.]

Conference

Title
2001 spring meeting of the Korean Nuclear Society
Dates
24-25 May 2001
Place
Cheju (Korea, Republic of)

INIS

Country of Publication
Korea, Republic of
Country of Input or Organization
Korea, Republic of
INIS RN
33040751
Subject category
S42: ENGINEERING;
Resource subtype / Literary indicator
Conference, Non-conventional Literature
Descriptors DEI
EVALUATION; FINITE ELEMENT METHOD; ICE; LEAKS; NUCLEAR POWER PLANTS; PIPES; PLUGGING; RECOMMENDATIONS; SAFETY
Descriptors DEC
CALCULATION METHODS; NUCLEAR FACILITIES; NUMERICAL SOLUTION; POWER PLANTS; THERMAL POWER PLANTS; TUBES

Optional Information

Notes
16 refs, 11 figs, 2 tabs