Air-water heat pump modelling for residential heating and domestic hot water in Chile

  • 1. Departamento de Ingeniería Mecánica, Universidad de Concepción, Edmundo Larenas 219, Concepción (Chile)

Description

Highlights: • A detailed model of a heat pump for heating and DHW is developed. • Chilean building characteristics and weather conditions are considered in the modelling. • Promising COPs values are obtained for a heat pump based heating and DHW heating. • Similar seasonal performance factors are obtained for Concepción and Santiago. In Chile, household heating demands are mainly provided by wood stoves and domestic hot water by gas water heater. This presents two drawbacks, the use of wood stoves for heating is responsible of severe pollution problems during winter period and another drawback is associated to the high price of the gas. To mitigate these problems, it is proposed to analyse the use of heat pumps for both heating and domestic hot water. The first step for this analysis is to determine the seasonal performance of the heat pump, which depends, among others, on the building location, building characteristics and heat pump characteristics. In this study the performance of a four occupants household located at Concepción and Santiago are considered. The heating demand is determined by using the software TRNSYS, by obtaining an annual heating demand that varies between 5003 kWh and 8788 kWh for Concepción and between 4388 kWh and 7883 kWh for Santiago. The domestic hot water demand is determined from a typical consumption profile, with an annual energy demand of 3721 kWh and 3541 kWh for Concepción and Santiago respectively. These profiles are used as inputs to the heat pump model by developing an hourly simulation. The heat pump is modelled by using a modular approach decomposed in three individual models for the following components: compressor, condenser and evaporator. It is assumed that the compressor is regulated with an ON/OFF control. The system SPF varies between 2,54 and 2,60 for the six cases analysed in this study. There is no significant difference in the SPF in both cities, which is attributed to the ambient conditions, which are in average very similar.

Availability note (English)

Available from http://dx.doi.org/10.1016/j.applthermaleng.2018.07.130

Additional details

Identifiers

DOI
10.1016/j.applthermaleng.2018.07.130;
PII
S1359431118308652;

Publishing Information

Journal Title
Applied Thermal Engineering
Journal Volume
143
Journal Page Range
p. 594-606
ISSN
1359-4311
CODEN
ATENFT

Optional Information

Copyright
Copyright (c) 2018 Elsevier Ltd. All rights reserved.