Published July 2010 | Version v1
Journal article

Tube failures due to cooling process problem and foreign materials in power plants

  • 1. Kapar Energy Ventures Sdn Bhd, Jalan Tok Muda, Kapar 42200 (Malaysia)
  • 2. Department of Mechanical Engineering, Universiti Tenaga Nasional, Km 7 Jalan Kajang-Puchong, Kajang 43009, Selangor (Malaysia)

Description

Cooling process which uses water for heat transfer is an essential factor in coal-fired and nuclear plants. Loss of cooling upset can force the plants to shut down. In particular, this paper reports visual inspections and metallurgical examinations on the failed SA210-A1 right-hand side (RHS) water wall tube of a coal-fired plant. The water wall tube showed the abnormal outer surface colour and has failed with wide-open ductile rupture and thin edges indicating typical signs of short-term overheating. Metallurgical examinations confirmed the failed tube experiencing higher temperature operation. Water flow starvation due to restriction inside the upstream tube is identified as the main root cause of failure. The findings are important to take failure mitigation actions in the future operation. Discussion on the typical problems related to the cooling process in nuclear power plants is also presented.

Availability note (English)

Available from http://dx.doi.org/10.1016/j.nucengdes.2010.03.022

Additional details

Identifiers

DOI
10.1016/j.nucengdes.2010.03.022;
PII
S0029-5493(10)00200-1;

Publishing Information

Journal Title
Nuclear Engineering and Design
Journal Volume
240
Journal Issue
7
Journal Page Range
p. 1882-1886
ISSN
0029-5493
CODEN
NEDEAU

Optional Information

Copyright
Copyright (c) 2010 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.