Published 2000 | Version v1
Miscellaneous

Wet surface performance test of PF heat exchanger

  • 1. Incheon Univ., Incheon (Korea, Republic of)

Description

In this study, the wet surface heat transfer coefficients and friction factors of PF heat exchangers are presented. Two sample with different fin pitch(1.25mm, 1.5mm) were tested. Tests were conducted in a open loop wind tunnel. The wet surface heat transfer coefficient was reduced following the procedure given in ARI 410-81. Results showed that the heat transfer coefficients of the heat exchanger with 1.5mm fin pitch were approximately the same as those with 1.25mm fin pitch, except at low Reynolds number(Re<100), where the heat transfer coefficients of 1.5mm fin pitch were slightly higher than those with 1.25mm fin pitch. The friction factors of the 1.25mm fin pitch, however was 120 % to 160 % higher than those of the 1.5mm fin pitch. The wet surface heat transfer coefficients were lower than those of the dry surface. The wet surface friction factors, however, were higher than those of the dry surface

Part of:
Proceedings of the KSME 2000 fall annual meeting B

Additional details

Publishing Information

Publisher
KSME
Imprint Place
Seoul (Korea, Republic of)
Imprint Title
Proceedings of the KSME 2000 fall annual meeting B
Imprint Pagination
770 p.
Journal Page Range
p. 314-320

Conference

Title
KSME 2000 fall annual meeting B
Dates
2-4 Nov 2000
Place
Seoul (Korea, Republic of)

INIS

Country of Publication
Korea, Republic of
Country of Input or Organization
Korea, Republic of
INIS RN
36066949
Subject category
S42: ENGINEERING;
Resource subtype / Literary indicator
Conference, Non-conventional Literature
Descriptors DEI
EVAPORATORS; FRICTION FACTOR; HEAT EXCHANGERS; HEAT TRANSFER; PERFORMANCE; REYNOLDS NUMBER; SURFACES
Descriptors DEC
DIMENSIONLESS NUMBERS; ENERGY TRANSFER

Optional Information

Notes
13 refs, 7 figs, 1 tab