Energy savings from temperature setpoints and deadband: Quantifying the influence of building and system properties on savings

  • 1. Sonny Astani Dept. of Civil and Environmental Engineering, Viterbi School of Engineering, Univ. of Southern California, KAP 217, 3620 South Vermont Ave., Los Angeles, CA 90089-2531 (United States)
  • 2. Sonny Astani Dept. of Civil and Environmental Engineering, Viterbi School of Engineering, Univ. of Southern California, KAP 224C, 3620 South Vermont Ave., Los Angeles, CA 90089-2531 (United States)

Description

Highlights: • We provide a systematic approach to quantify the impact of factors on energy usage. • We study setpoints, deadbands, building size, construction, occupancy, and climate. • We derive the HVAC optimal control parameters with respect to dynamic factors. • We present quantification of optimal setpoints and deadbands energy usages. • Daily optimal setpoints based on outside temperature improves energy efficiency. - Abstract: This paper provides a systematic approach for quantifying the influence of building size, construction category, climate, occupancy schedule, setpoint, and deadband on HVAC energy consumption in office buildings. Simulating the DOE reference office buildings of three sizes and three construction categories in all United States climate zones, using the EnergyPlus, we conducted several N-way ANOVA analyses to study the interrelationships between setpoints, deadbands and several building related and environment related factors. In summary, daily optimal deadband selection of 0, 1, 2, 4, 5, and 6 K would result in an average energy savings of −70.0%, −34.9%, −13.7%, 9.6%, 16.4%, and 21.2%, respectively, compared to baseline deadline of 3 K. Selecting the daily optimal setpoint in the range of 22.5 ± 1 °C, 22.5 ± 2 °C, and 22.5 ± 3 °C would result in an average savings of 7.5%, 12.7%, and 16.4%, respectively, compared to the baseline setpoint of 22.5 °C. Additionally, we found that when the outdoor temperature is within −20 to 30 °C, the optimal setpoint depends on the building size. We also observed a range of outdoor temperatures (e.g., 9–14 °C for small buildings and 8–11 °C for medium buildings) where the setpoint selection would only slightly influence the energy consumption. However, the choice of setpoints becomes very influential (up to 30% of energy savings) where the outdoor temperatures are slightly outside the mentioned ranges on either direction. The potential savings from selecting daily optimal setpoints in the range of 22.5 ± 3 °C in different climates and for small, medium and large office buildings, would lead to 10.09–37.03%, 11.43–21.01%, and 6.78–11.34% savings, respectively, depending on the climate.

Availability note (English)

Available from http://dx.doi.org/10.1016/j.apenergy.2015.12.115

Additional details

Identifiers

DOI
10.1016/j.apenergy.2015.12.115;
PII
S0306-2619(15)01688-8;

Publishing Information

Journal Title
Applied Energy
Journal Volume
165
Journal Page Range
p. 930-942
ISSN
0306-2619
CODEN
APENDX

INIS

Country of Publication
United Kingdom
Country of Input or Organization
International Atomic Energy Agency (IAEA)
INIS RN
48001414
Subject category
S29: ENERGY PLANNING, POLICY AND ECONOMY;
Descriptors DEI
CLIMATES; COMPARATIVE EVALUATIONS; ENERGY CONSUMPTION; ENERGY EFFICIENCY; ENVIRONMENT; HVAC SYSTEMS; OFFICE BUILDINGS; OPTIMAL CONTROL; OUTDOORS; US DOE
Descriptors DEC
AC SYSTEMS; BUILDINGS; CONTROL; EFFICIENCY; ENERGY SYSTEMS; EVALUATION; NATIONAL ORGANIZATIONS; POWER SYSTEMS; US ORGANIZATIONS

Optional Information

Copyright
Copyright (c) 2015 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.