Published March 2001 | Version v1
Report Open

ChemAND - a system health monitor for plant chemistry

  • 1. Atomic Energy of Canada Limited, Chalk River, Ontario (Canada)
  • 2. Hydro-Quebec, Groupe Chimie, Centrale Nucleaire Gentilly-2, Gentilly, Quebec (Canada)

Description

Effective management of plant systems throughout their lifetime requires much more than data acquisition and display - it requires that the plant's system health be continually monitored and managed. AECL has developed a System Health Monitor called ChemAND for CANDU plant chemistry. ChemAND, a Chemistry ANalysis and Diagnostic system, monitors key chemistry parameters in the heat transport system, moderator-cover gas, annulus gas, and the steam cycle during full-power operation. These parameters can be used as inputs to models that calculate the effect of current plant operating conditions on the present and future health of the system. Chemistry data from each of the systems are extracted on a regular basis from the plant's Historical Data Server and are sorted according to function, e.g., indicators for condenser in-leakage, air in-leakage, heavy water leakage into the annulus gas, fuel failure, etc. Each parameter is conveniently displayed and is trended along with its alarm limits. ChemAND currently includes two analytical models developed for the balance-of-plant. The first model, ChemSolv, calculates crevice chemistry conditions in the steam generator (SG) from either the SG blowdown chemistry conditions or from a simulated condenser leak. This information can be used by plant staff to evaluate the susceptibility of the SG tubes to crevice corrosion. ChemSolv also calculates chemistry conditions throughout the steam-cycle system as determined by the transport of volatile species such as ammonia, hydrazine, morpholine, and oxygen. The second model, SLUDGE, calculates the deposit loading and distribution in the SG as a function of time, based on concentrations of corrosion product in the final feedwater for both normal and start-up conditions. Operations personnel can use this information to predict where to inspect and when to clean. (author)

Availability note (English)

Available from INIS in electronic form

Files

34073616.pdf

Files (743.8 kB)

Name Size Download all
md5:24f513e5d8abe5b4d354282fa9dc3624
743.8 kB Preview Download

Additional details

Publishing Information

Imprint Pagination
17 p.
Report number
AECL--12117

Conference

Title
5. Canadian Nuclear Society international conference on CANDU maintenance
Dates
12-21 Nov 2000
Place
Toronto, Ontario (Canada)

Optional Information

Notes
3 refs., 8 figs.