Determination of preventive maintenance periodicities of standby devices

Description

This article presents a statistical approach of analysis and decision that uses reliability techniques to define the best periodicity for preventive maintenance of power system protective relays. Relays are standby devices and may stay in the hidden failure state when they are not working. This state of failure generates difficulties in the determination of preventive maintenance periodicities. A case study presented in this work deals specifically with the reliability of the transmission and distribution system protective relays of CEMIG (the state owned Electrical Power Company of Minas Gerais, Brazil). Preventive maintenance data of protective relays obtained during a 4-year period were used in the proposed method. The choice of the periodicities, distinguished by groups of similar relay and voltage operation levels of the protected systems, is made according to the failure risk level that the company is willing to take. The main result obtained by using this method is a substantial reduction of 62% in the amount of preventive maintenance work load for the relays of the distribution system

Additional details

Identifiers

PII
S095183200100134X;

Publishing Information

Journal Title
Reliability Engineering and System Safety
Journal Volume
76
Journal Issue
2
Journal Page Range
p. 149-154
ISSN
0951-8320
CODEN
RESSEP

INIS

Country of Publication
United Kingdom
Country of Input or Organization
International Atomic Energy Agency (IAEA)
INIS RN
36072400
Subject category
S25: ENERGY STORAGE; S99: GENERAL AND MISCELLANEOUS;
Descriptors DEI
FAILURES; MAINTENANCE; PERIODICITY; POWER SYSTEMS; POWER TRANSMISSION; RELAYS; RELIABILITY; RISK ASSESSMENT