Determination of the exposition rapidity in the level 49.90 of the reactor building for the decrease in the water level of the spent fuel pool

  • 1. Comision Federal de Electricidad, Central Nucleoelectrica Laguna Verde, Subgerencia de Ingenieria, Km 44.5 Carretera Cardel-Nautla, 91476 Laguna Verde, Alto Lucero, Veracruz (Mexico)

Description

The fuel assemblies storage in the nuclear power plant of Laguna Verde (NPP-L V) represents a crucial aspect, due to the generated dose by the decay heat of the present radio-nuclides in the assemblies retired of the reactor core, after their useful life. These spent assemblies are located inside the spent fuel pool (SFP), in the level 49.90 m in the Reload Floor of the Reactor building of NPP-L V. This leads to the protection at personnel applying the ALARA (As Low As Reasonably Achievable) criteria, fulfilling the established dose criteria by the Regulator Body the Comision Nacional de Seguridad Nuclear y Salvaguardias (CNSNS). Considering the loss scenario of the cooling system of the SFP, in which the SFP water vaporizes, is important to know the water level in which the limit of effective dose equivalent is fulfilled for the personnel. Also, is important for the instrumentation of the SFP, for the useful life of the same instruments. In this work is obtained the exposition rapidity corresponding to different water levels of SFP in the Reload Floor of NPP-L V, to identify the minimum level of water where the limit of effective dose equivalent is fulfilled of 25 rem s to the personnel, established in the Article 48 of the General Regulation of Radiological Safety of CNSNS and the Chapter 50 Section 67 of the 10-Cfr of Nuclear Regulatory Commission in USA. The water level is also identified where the exposition rapidity is of 15 m R/hr, being the value of the set point of the area radiation monitor D21-Re-N003-1, located to 125 cm over the level 49.90 meters of the Reload Floor of NPP-L V. (Author)

Availability note (English)

Available from the Instituto Nacional de Investigaciones Nucleares, Centro de Informacion y Documentacion, 52750 Ocoyoacac, Estado de Mexico (Mexico), e-mail: mclaudia.gonzalez@inin.gob.mx

Additional details

Additional titles

Original title (Spanish)
Determinacion de la rapidez de exposion en el nivel 49.90 del edificio del reactor por la disminucion en el nivel de agua de la alberca de combustible gastado

Publishing Information

Publisher
Sociedad Nuclear Mexicana
Imprint Place
Mexico D. F. (Mexico)
Imprint Pagination
27 p.

Conference

Title
the nuclear challenges; life extension, safety, public perception and reactors of new generation
Original Conference Title
25. Congreso Anual de la SNM
Acronym
25. SNM Annual Congress; 13. SMSR National Congress
Dates
31 Aug - 4 Sep 2014
Place
Boca del Rio, Veracruz (Mexico)