This report presents the methodology and documentation of the calibration of the Loss-of-Fluid Test (LOFT) power-operated relief and safety relief valve (PORV + SRV) for the L9-3 anticipated transient without scram (ATWS) experiment. A multiposition globe valve was calibrated to produce scaled high-pressure flow rates using a low-pressure calibration facility and a simple RELAP5 critical flow model to extrapolate the calibration data to expected operating pressures. It was demonstrated that an accurate high-pressure, multiphase flow calibration can be performed without the necessity of actual high-pressure testing. This technique, when applied to large pressurized water reactor (LPWR) safety and relief valves, represents a potentially large savings in the capacity qualification procedure of full-scale pressure reduction valves

Availability note (English)

MF available from INIS under the Report Number; Available from NTIS, PC A02/MF A01 - GPO as TI85009842.

Files

Restricted

The record is publicly accessible, but files are restricted to users with access.

Additional details

Additional titles

Augmented title (English)
L9-3 ATWS experiment in LOFT

Publishing Information

Imprint Pagination
26 p.
Report number
NUREG/CR--4046

Optional Information

Secondary number(s)
EGG--2357.