Published December 1992 | Version v1
Journal article

Simulations and field tests of a reactor coolant pump emergency start-up by means of remote gas units

  • 1. Elektroinstitut M. Vidmar, Faculty for Electrical Engineering and Computer Science, Ljubljana, Slovenia (Yugoslavia)

Description

The problem of the reactor coolant pump start-up in case of emergency by means of remote gas power plant units was analyzed. In this paper a simulation model is developed which enabled a detailed simulation of the transient process occurring at the start-up. The start-up of the RCP motor set was simulated in case of available one and two gas units. The field tests were performed and the measured variable values complied well with the simulation results. Two gas units have been determined as a safe start-up scheme of the RCP motor set considering for safety reasons accepted busbars and motor protection settings. A derived model for deep rotor bars was experimentally confirmed as effective means for the RCP motor set start-up transient simulation. Start-up procedures have been designed and adopted to the safety procedures of the Nuclear Power Plant Krsko

Additional details

Publishing Information

Journal Title
IEEE Transactions on Energy Conversion
Journal Volume
7
Journal Issue
4
Journal Page Range
p. 691-697.
ISSN
0885-8969
CODEN