Published June 2006 | Version v1
Journal article

Technoeconomic appraisal of a ground source heat pump system for a heating season in eastern Turkey

  • 1. Department of Mechanical Education, Faculty of Technical Education, Firat University, 23119 Elazig (Turkey)
  • 2. Department of Mechanical Engineering, Faculty of Engineering, Firat University, 23119 Elazig (Turkey)

Description

In this study, performance experiments and economic analysis of a horizontal ground source heat pump (GSHP) system have been performed. The horizontal GSHP system connected to a test room, Elazig (38.41oN, 39.14oE), Turkey, was designed and constructed for space heating. The heating and cooling loads of the test room were 2.5 and 3.1 kW at design conditions, respectively. The performance was determined experimentally under real operational conditions. The experimental results were obtained from 7 November 2002 to 3 May 2003 in the heating season of 2002-2003. A detailed cost analysis was presented and payback periods when substituting for different local fuel/power sources were determined. The GSHP system was compared to conventional heating methods (electric resistance, fuel oil, liquid petrol gas, coal, oil and natural gas) in the economical analysis using an annualised life cycle cost method. It was shown that the GSHP system offers economic advantages over the mentioned first five conventional heating methods. However, it is not an economic alternative system to natural gas

Additional details

Identifiers

DOI
10.1016/j.enconman.2005.06.024;
PII
S0196-8904(05)00175-5;

Publishing Information

Journal Title
Energy Conversion and Management
Journal Volume
47
Journal Issue
9-10
Journal Page Range
p. 1281-1297
ISSN
0196-8904
CODEN
ECMADL

Optional Information

Copyright
Copyright (c) 2005 Elsevier Science B.V., Amsterdam, The Netherlands, All rights reserved.