Published May 1983 | Version v1
Report Restricted

Loss of DHR sequences at Browns Ferry Unit One - accident-sequence analysis

Description

This study describes the predicted response of Unit One at the Browns Ferry Nuclear Plant to a postulated loss of decay heat removal (DHR) capability following scram from full power with the power conversion system unavailable. In accident sequences without DHR capability, the residual heat removal (RHR) system functions of pressure suppression pool cooling and reactor vessel shutdown cooling are unavailable. Consequently, all decay heat energy is stored in the pressure suppression pool with a concomitant increase in pool temperature and primary containment pressure. With the assumption that DHR capability is not regained during the lengthy course of this accident sequence, the containment ultimately fails by overpressurization. Although unlikely, this catastrophic failure might lead to loss of the ability to inject cooling water into the reactor vessel, causing subsequent core uncovery and meltdown. The timing of these events and the effective mitigating actions that might be taken by the operator are discussed in this report

Availability note (English)

MF available from INIS under the Report Number; Available from NTIS, PC A09/MF A01; 1 as DE83012314.

Files

Restricted

The record is publicly accessible, but files are restricted to users with access.

Additional details

Publishing Information

Imprint Pagination
176 p.
Report number
NUREG/CR--2973

Optional Information

Secondary number(s)
ORNL/TM--8532.