Prevention of false alarms from automatic fire alarm system in the Tokai Reprocessing Plant
- 1. Japan Atomic Energy Agency, Nuclear Fuel Cycle Engineering Laboratories, Tokai, Ibaraki (Japan)
Description
The automatic fire alarm system installed in the Tokai Reprocessing Plant consists of more than 5,000 detectors in about 40 facilities for the moment. In this system, 51 non-fire cases have occurred for about 8 years from January 2001 to May 2009 and about half of these cases was due to the condensation of water vapor generated on the sensor. Therefore, the prevention of condensation is necessary to reduce such false alarms, and the measure for prevention of condensation has been taken by installing a mount for the detector basement. This mount facilitates that the detector does not contact directly to the surface of ceiling where is likely to change an environment due to changeable temperature and humidity. As a result, false alarms caused by condensation have not been found on the detectors with the mounts. This paper reports the details of the improved fire alarm system, and cause/measures for false alarms. (author)
Additional details
Additional titles
- Original title (Japanese)
- Nippon hozen gakkai dai-6-kai gakujutsu koenkai yoshishu
Publishing Information
- Imprint Title
- Proceedings of the 6th annual meeting of Japan Society of Maintenology
- Imprint Pagination
- 601 p.
- Journal Page Range
- p. 289-293
Conference
- Title
- 6. annual meeting of Japan Society of Maintenology
- Dates
- 3-5 Aug 2009
- Place
- Sapporo (Japan)
INIS
- Country of Publication
- Japan
- Country of Input or Organization
- Japan
- INIS RN
- 41116475
- Subject category
- S11: NUCLEAR FUEL CYCLE AND FUEL MATERIALS;
- Resource subtype / Literary indicator
- Conference, Non-conventional Literature
- Descriptors DEI
- ACCIDENTS; ALARM SYSTEMS; ERRORS; FIRE DETECTORS; FIRES; HUMIDITY; MONTHLY VARIATIONS; SYSTEM FAILURE ANALYSIS; TOKAI REPROCESSING PLANT; VAPOR CONDENSATION
- Descriptors DEC
- FUEL REPROCESSING PLANTS; MEASURING INSTRUMENTS; MOISTURE; NUCLEAR FACILITIES; SYSTEMS ANALYSIS; VARIATIONS
Optional Information
- Notes
- 2 refs., 9 figs. Imprint:Nippon hozen gakkai dai-6-kai gakujutsu koenkai yoshishu