Published November 1980 | Version v1
Journal article

Dangers of bypassing thermal overload relays in nuclear power plant motor operated valve circuits

Creators

  • 1. Yankee At Electr Co, Westboro, Mass

Description

Operation of motor operated valves is analyzed under various abnormal conditions such as frozen bearing, tight packing, mid-travel obstruction, torque switch failure, limit switch failure, and post-accident operation. Each condition has been reviewed to show that an adverse situation results if the thermal overload relays in the circuit are bypassed. In conclusion, there appears to be no technical basis for bypassing or oversizing the thermal overload relay provided it is selected correctly

Additional details

Publishing Information

Journal Title
IEEE Trans. Power Appar. Syst.
Journal Volume
PAS-99
Journal Issue
6
Series
IEEE Trans. Power Appar. Syst.
Journal Page Range
2287-2291
ISSN
0018-9510

INIS

Country of Publication
United States
Country of Input or Organization
United States
INIS RN
12632859
Subject category
S22: GENERAL STUDIES OF NUCLEAR REACTORS;
Descriptors DEI
EQUIPMENT PROTECTION DEVICES; NUCLEAR POWER PLANTS; RELAYS; SPECIFICATIONS; TEMPERATURE DEPENDENCE; VALVES
Descriptors DEC
CONTROL EQUIPMENT; ELECTRICAL EQUIPMENT; FLOW REGULATORS; NUCLEAR FACILITIES; POWER PLANTS; THERMAL POWER PLANTS