Operation of motor operated valves is analyzed under various abnormal conditions such as frozen bearing, tight packing, mid-travel obstruction, torque switch failure, limit switch failure, and post-accident operation. Each condition has been reviewed to show that an adverse situation results if the thermal overload relays in the circuit are bypassed. In conclusion, there appears to be no technical basis for bypassing or oversizing the thermal overload relay provided it is selected correctly