Published 1997
| Version v1
Miscellaneous
Zero current measurements using the Rogowski coil
- 1. Dept. of Special Electrical Engineering and Quality FEEI TU Brno, Brno (Czech Republic)
- 2. Dept. of Electrical Machines and Apparatuses FEEI TU Brno, Brno (Czech Republic)
Description
The zero current measurements using the Rogowski coil carried out on the model of the extinguishing chamber of hv SF6 circuit breaker with self-flow generation are presented in the paper. The time course of the post-arc current obtained by numerical integration of the measured induced voltage of the Rogowski coil gives information not only about the value of the residual current after the successful interruption but also about the current changes connected with the dynamic behaviour of the arc during its quenching. (author)
Additional details
Publishing Information
- ISBN
- 83-87198-20-X
- Imprint Title
- Conference materials (Part 1)
- Imprint Pagination
- 407 p.
- Journal Page Range
- p. 268-270.
Conference
- Title
- 8. international conference on switching arc phenomena with satellite international symposium on electrical technologies for environmental protection.
- Original Conference Title
- 8 miedzynarodowa konferencja elektryczny luk laczeniowy z towarzyszacym sympozjum elektrotechnologie ochrony srodowiska
- Dates
- 3-6 Sep 1997.
- Place
- Lodz (Poland).
INIS
- Country of Publication
- Poland
- Country of Input or Organization
- Poland
- INIS RN
- 29023320
- Subject category
- S70: PLASMA PHYSICS AND FUSION TECHNOLOGY;
- Resource subtype / Literary indicator
- Conference, Non-conventional Literature
- Descriptors DEI
- CIRCUIT BREAKERS; DISCHARGE QUENCHING; ELECTRIC ARCS; ELECTRIC CURRENTS; MEASURING METHODS; MEETINGS; PLASMA DIAGNOSTICS; ROGOWSKI COIL
- Descriptors DEC
- CURRENTS; ELECTRIC COILS; ELECTRIC DISCHARGES; ELECTRICAL EQUIPMENT; EQUIPMENT; EQUIPMENT PROTECTION DEVICES
Optional Information
- Notes
- 2 refs, 6 figs.