Published August 2002 | Version v1
Journal article

Verification of control system using inverter and canned motor pump

  • 1. Japan Atomic Power Co., Tokyo (Japan)
  • 2. Teikoku Electric MFG. Co., Ltd. (Japan)

Description

Control on flow volume and so on of auxiliary systems at power stations is generally carried out by using control valves (CVs), of which numbers and kinds ranges to wide areas. CVs are required for periodical change of packing and so on, of which labor for maintenance is never few. Therefore, to reduce the maintenance of CVs, a system to operate pumps by using an inverter control was investigated. When carrying out flow control by an inverter, valves at output side of pumps was made perfectly open, but because of control on rotation numbers so as to keep required amount excess energy is never consumed. And, by reducing flow volume of a pump, consumed energy is reduced at a rate of its three powers as feature of pumps, so large energy saving effect can be established. Selected canned motor pumps have such characteristics as upgrading of reliability for leakage because of their seal-less ones and extension of periodical inspection period by setting a monitor for abrasion of bearings. As results of some investigations, it could be considered that a control system combining an inverter with a canned motor pump had equal feature as that of a control system using CVs. And, from a test result adding useless time and first order delay element to its control feature forecasting on its application to practical machine could be obtained. (G.K.)

Additional details

Publishing Information

Journal Title
Karyoku Genshiryoku Hatsuden
Journal Volume
53
Journal Issue
8
Journal Page Range
p. 925-933
ISSN
0387-1029