Bromination vis-a-vis chlorination as a biocide feasibility study
Creators
- 1. Nuclear Power Corporation, Narora Atomic Power Station, Narora (India)
Description
Water is used extensively as a cooling medium in various heat transfer equipment's of a power industry such as condenser, heat exchangers and cooling towers. At elevated temperature, the breeding of microbiological growth can form slimes, underneath of this, accelerated corrosion can take place resulting into sudden and catastrophic failure of equipment's. The microbiological growth unchecked in the various systems especially in low velocity areas can lead to large growth of micro organisms such as algae which can even reduce the flow of the fluid thus affecting the efficiency of plant equipment's. Therefore, chlorination is a mandatory requirement in industrial cooling water to reduce biofouling in heat transfer equipment's. The chlorination in drinking water produces germicidal effect and thus reduces the bacterial counts. At NAPS the water quality is good and mild doses of chlorine (5 ppm) two times a day, as envisaged in design is noticed to be satisfactory. The chlorination of recirculating condenser cooling water presently is being done with the established doses for a fixed time twice a day. Some of the problems noticed with the chlorination process are : Corrosion of constructional material of chlorination plant and equipment's and pipelines causing large input of efforts on maintenance for keeping high availability of the chlorination plant. In addition to this, the leakages in the equipment could be a potential safety hazard. The effectiveness of chlorine is observed to be less in alkaline pH (above 9.0) as encountered at NAPS. This results is large quantities of chlorine injection for extended periods. The cost of chlorine and bleaching powder keeps fluctuating in the market as noticed in past few years. Many a times this results in scarcity of chlorine/bleaching powder causing interruption in biofouling control programme. Hence it was felt prudent to work on the alternative biocides which could be cost effective, non-polluting and nature and user friendly. This paper highlights the brief details on the feasibility studies carried out on bromination. (author)
Additional details
Publishing Information
- Publisher
- Bhabha Atomic Research Centre
- Imprint Place
- Mumbai (India)
- Imprint Title
- Proceedings of the national symposium on water and steam chemistry in power plants and industrial units
- Imprint Pagination
- 680 p.
- Journal Page Range
- p. 456-463
Conference
- Title
- national symposium on water and steam chemistry in power plants and industrial units
- Acronym
- SWASCH-2000
- Dates
- 23-25 Feb 2000
- Place
- Mumbai (India)
INIS
- Country of Publication
- India
- Country of Input or Organization
- India
- INIS RN
- 32044628
- Subject category
- S21: SPECIFIC NUCLEAR REACTORS AND ASSOCIATED PLANTS;
- Resource subtype / Literary indicator
- Conference
- Descriptors DEI
- ALGAE; BIOLOGICAL FOULING; BROMINATION; CHLORINATION; CONDENSER COOLING SYSTEMS; CORROSION; ENVIRONMENTAL IMPACTS; NARORA-1 REACTOR; NARORA-2 REACTOR; REACTOR COOLING SYSTEMS; RECOMMENDATIONS; WATER CHEMISTRY; WATER TREATMENT
- Descriptors DEC
- AUXILIARY SYSTEMS; AUXILIARY WATER SYSTEMS; CHEMICAL REACTIONS; CHEMISTRY; COOLING SYSTEMS; ENERGY SYSTEMS; FOULING; HALOGENATION; HEAVY WATER COOLED REACTORS; HEAVY WATER MODERATED REACTORS; NATURAL URANIUM REACTORS; PHWR TYPE REACTORS; PLANTS; POWER REACTORS; REACTOR COMPONENTS; REACTORS
Optional Information
- Notes
- 1 fig., 7 tabs.